UBiBOT UB-VS-N1 External Vibration Sensor

ຂໍ້ມູນຈໍາເພາະຂອງຜະລິດຕະພັນ
- ຕົວແບບ: UB-VS-N1
- ການສະຫນອງພະລັງງານ: 3 * AA batteries, 4.5V
- ປັດຈຸບັນສູງສຸດ: 306mA
- ໄລຍະການວັດແທກ: Maximum vibration value: 0~1000
- ສະພາບແວດລ້ອມການເຮັດວຽກ: -40~60°C, 0~80%RH
- ຄວາມຍາວສາຍເຊື່ອມຕໍ່: 3m
- ອະນຸສັນຍາການສື່ສານ: RS485 Modbus RTU Protocol
- RS485 ທີ່ຢູ່: 0x41
- ອັດຕາ Baud: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s (ຄ່າເລີ່ມຕົ້ນ), 19200 bit/s
ຄໍາແນະນໍາການນໍາໃຊ້ຜະລິດຕະພັນ
ອະນຸສັນຍາການສື່ສານ
- Coding System: Modbus-RTU
- Data Bit: 8 bits
- Parity Checking Bit: ບໍ່ມີ
- Stop Bit: 1 ບິດ
- Error Checking: CRC Check
- Baud Rate: Select from available options.
ຮູບແບບກອບຂໍ້ມູນDetailed information on the Modbus-RTU communication protocol format is provided in the manual for reference.
ແນະນຳຜະລິດຕະພັນ
The vibration sensor adopts the original imported sensor, built-in 5 batteries, can be continuously measured, stable data, high precision, strong anti-interference ability, long service life.
ໃຊ້ສະຖານະການກໍລະນີ
Suitable for environmental equipment rooms, airports, railway stations, commercial building control, family homes, office buildings, schools, conference rooms, shopping malls, hotels, gymnasiums, cinemas, libraries and other places.
ຄຸນສົມບັດ
- Real-time monitoring of vibration values.
- Suspension or stick-on mounting for ease of use.
ຂໍ້ມູນຈໍາເພາະຂອງຜະລິດຕະພັນ
| ຂໍ້ມູນຈໍາເພາະ | |
| ຕົວແບບ | UB-VS-N1 |
| ການສະຫນອງພະລັງງານ | 3 *AA batteries(4.5V) |
| ປະຈຸບັນສູງສຸດທີ່ເຄຍ | 306mA |
| ໄລຍະການວັດແທກ | Maximum vibration value: 0~1000 |
| ສະພາບແວດລ້ອມການເຮັດວຽກ | -40~60℃, 0~80%RH |
| ຕົວເຊື່ອມຕໍ່ | ສຽງ |
| ຄວາມຍາວສາຍ | 3m |
| ອະນຸສັນຍາການສື່ສານ | RS485 Modbus RTU Protocol |
| RS485 ທີ່ຢູ່ | 0x41 |
| ອັດຕາ Baud | 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s (ຄ່າເລີ່ມຕົ້ນ), 19200 bit/s |
ຄໍາແນະນໍາສາຍໄຟ
ອະນຸສັນຍາການສື່ສານ
ຕົວກໍານົດການພື້ນຖານການສື່ສານ
| ພາຣາມິເຕີພື້ນຖານການສື່ສານ | |
| ລະບົບລະຫັດ | 8-ບິດຖານສອງ |
| ຂໍ້ມູນນ້ອຍ | 8 ບິດ |
| Parity Checking Bit | ບໍ່ມີ |
| ຢຸດບິດ | 1 ບິດ |
| ການກວດສອບຄວາມຜິດພາດ | ການກວດສອບ CRC |
| ອັດຕາ Baud | 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s (ຄ່າເລີ່ມຕົ້ນ), 19200 bit/s |
ຮູບແບບກອບຂໍ້ມູນ
ໂປຣໂຕຄອນການສື່ສານ Modbus-RTU ຖືກນໍາໃຊ້ໃນຮູບແບບດັ່ງຕໍ່ໄປນີ້:
- ໂຄງສ້າງເບື້ອງຕົ້ນ ≥ 4 bytes ໃນເວລາ.
- ລະຫັດທີ່ຢູ່: 1 byte, ຄ່າເລີ່ມຕົ້ນ 0x41.
- ລະຫັດຟັງຊັນ: 1 byte, ຮອງຮັບລະຫັດຟັງຊັນ 0x03 (ອ່ານເທົ່ານັ້ນ) ແລະ 0x06 (ອ່ານ/ຂຽນ).
- ພື້ນທີ່ຂໍ້ມູນ: N bytes, ຂໍ້ມູນ 16-bit, byte ສູງມາກ່ອນ.
- ກວດສອບຂໍ້ຜິດພາດ: ລະຫັດ CRC 16-ບິດ.
- ໂຄງສ້າງສິ້ນສຸດ ≥ 4 bytes ຂອງເວລາ.
| ຮ້ອງຂໍ | ||||||||||||
| ທີ່ຢູ່ສໍາລອງ | ລະຫັດ ໜ້າ ທີ່ | ທີ່ຢູ່ລົງທະບຽນ | ໝາຍເລກທະບຽນ | CRC LSB | CRC MSB | |||||||
| 1 ໄບຕ໌ | 1 ໄບຕ໌ | 2 ໄບຕ໌ | 2 ໄບຕ໌ | 1 ໄບຕ໌ | 1 ໄບຕ໌ | |||||||
| ຕອບສະໜອງ | ||||||||||||
| ທີ່ຢູ່ສໍາລອງ | ລະຫັດ ໜ້າ ທີ່ | ໝາຍເລກຂອງໄບຕ໌ | ເນື້ອຫາ 1 | ເນື້ອຫາ 1 | … | ເນື້ອໃນ n | CRC | |||||
| 1 ໄບຕ໌ | 1 ໄບຕ໌ | 1 ໄບຕ໌ | 2 ໄບຕ໌ | 2 ໄບຕ໌ | … | 2 ໄບຕ໌ | 2 ໄບຕ໌ | |||||
ທີ່ຢູ່ລົງທະບຽນ
| ທີ່ຢູ່ລົງທະບຽນ | ||||
| ທີ່ຢູ່ | ເນື້ອໃນ | ໄລຍະເວລາລົງທະບຽນ | ລະຫັດ ໜ້າ ທີ່ | ຄໍາອະທິບາຍຄໍານິຍາມ |
| 0x0000 | ຫມໍ້ໄຟ Voltage | 1 | 03 | Unsigned integer data,
divided by 100 |
| 0x0001 | Cumulative activity time in cycle | 1 | 03 | ຈຳນວນເຕັມ |
| 0x0002 | Maximum vibration value during the cycle
(default cycle 60s) |
1 | 03 | ຈຳນວນເຕັມ |
| 0x0003 | Cumulative vibration value during the cycle
(default period 60s) |
1 | 03 | ຈຳນວນເຕັມ |
| 0x0004 | Accumulated activity time during runtime
(cleared after each acquisition) |
2 | 03 | ຈຳນວນເຕັມ |
|
0x0006 |
Maximum vibration value during cumulative runtime (cleared for re-collection after each
acquisition) |
2 |
03 |
ຈຳນວນເຕັມ |
| 0x0008 | Total vibration value during cumulative
runtime (cleared after each acquisition) |
2 | 03 | ຈຳນວນເຕັມ |
| 0x000A | Accumulated runtime in s (clear to re-
collect the time after each acquisition) |
2 | 03 | ຈຳນວນເຕັມ |
| ຂະ ໜາດ 0x000C | Activity time during cumulative runtime | 2 | 03 | ຈຳນວນເຕັມ |
|
0x000E |
Maximum vibration value during cumulative runtime (emptied and re-collected after
each acquisition) |
2 |
03 |
ຈຳນວນເຕັມ |
| 0x0010 | Total vibration value during cumulative
runtime (cleared after each acquisition) |
2 | 03 | ຈຳນວນເຕັມ |
| 0x0014 | X-axis acceleration | 1 | 03 | ຈຳນວນເຕັມທີ່ເຊັນແລ້ວ |
| 0x0015 | ການເລັ່ງແກນ Y | 1 | 03 | ຈຳນວນເຕັມທີ່ເຊັນແລ້ວ |
| 0x0016 | Z-axis acceleration | 1 | 03 | ຈຳນວນເຕັມທີ່ເຊັນແລ້ວ |
| 0x0017 | ຄວາມເລັ່ງທັງຫມົດ | 1 | 03 | ຈຳນວນເຕັມທີ່ເຊັນແລ້ວ |
| 0x0064 | ທີ່ຢູ່ | 1 | 03/06 | 1–255 |
| 0x0065 | ອັດຕາ Baud |
1 |
03/06 | 1: 4800, 2: 9600, 3:14400, 4:
19200, 5: 38400, 6: 115200 |
ໝາຍເຫດ
- ຫ້າມດຶງສາຍນຳຂອງເຊັນເຊີ, ຢ່າຫຼຸດ ຫຼືຕີເຊັນເຊີຢ່າງຮຸນແຮງ.
- Do not expose the sensor to high temperatures or long term exposure to steam, water mist, water curtains or condensation..
ຄໍາຖາມທີ່ຖາມເລື້ອຍໆ
Q: What is the recommended working temperature range for the vibration sensor?
A: The recommended working temperature range is -40°C to 60°C.
ຖາມ: ຂ້ອຍຈະກວດສອບແບດເຕີລີ່ voltage ຂອງເຊັນເຊີ?
A: Refer to register address 0x0000 to access the battery voltage ຂໍ້ມູນ.
ເອກະສານ / ຊັບພະຍາກອນ
![]() |
UBiBOT UB-VS-N1 External Vibration Sensor [pdf] ຄູ່ມືຜູ້ໃຊ້ UB-VS-N1 External Vibration Sensor, UB-VS-N1, External Vibration Sensor, Vibration Sensor, Sensor |