Danfoss MCI 15

ຄູ່ມືການໃຊ້ງານຕົວຄວບຄຸມມໍເຕີ Danfoss MCI 15 037N0039

1. ບົດແນະນຳ

This manual provides essential information for the safe and effective installation, operation, and maintenance of the Danfoss MCI 15 Motor Controller, model 037N0039. Please read this manual thoroughly before attempting to install or operate the device. Retain this manual for future reference.

2. ຂໍ້ມູນຄວາມປອດໄພ

ປະຕິບັດຕາມຄວາມລະມັດລະວັງດ້ານຄວາມປອດໄພຕໍ່ໄປນີ້ສະເໝີເພື່ອປ້ອງກັນການບາດເຈັບສ່ວນບຸກຄົນ ຫຼືຄວາມເສຍຫາຍຕໍ່ອຸປະກອນ:

  • ການຕິດຕັ້ງແລະການບໍາລຸງຮັກສາຄວນຈະຖືກປະຕິບັດໂດຍບຸກຄະລາກອນທີ່ມີຄຸນວຸດທິເທົ່ານັ້ນ.
  • ໃຫ້ແນ່ໃຈວ່າການປິດການສະຫນອງພະລັງງານກ່ອນທີ່ຈະດໍາເນີນການສາຍຫຼືການບໍາລຸງຮັກສາ.
  • ກວດ​ສອບ​ການ​ເຊື່ອມ​ຕໍ່​ທັງ​ຫມົດ​ແມ່ນ​ປອດ​ໄພ​ແລະ​ມີ​ສາຍ​ຢ່າງ​ຖືກ​ຕ້ອງ​ອີງ​ຕາມ​ແຜນ​ວາດ​ທີ່​ສະ​ຫນອງ​ໃຫ້​.
  • ປົກປ້ອງອຸປະກອນຈາກຄວາມຊຸ່ມຊື່ນ, ຂີ້ຝຸ່ນ, ແລະອຸນຫະພູມທີ່ຮຸນແຮງ.
  • Do not operate the controller if it appears damaged.

3. ຜະລິດຕະພັນເກີນview

The Danfoss MCI 15 Motor Controller is designed for controlling motor speed and soft starting applications. It features robust construction with an integrated heat sink for efficient thermal management.

ໂດຍລວມ view of the Danfoss MCI 15 Motor Controller
ຮູບທີ 3.1: ໂດຍລວມ view of the Danfoss MCI 15 Motor Controller, showing the front panel with branding and specifications, and the heat sink fins.
Close-up of the control panel of the Danfoss MCI 15 Motor Controller
Figure 3.2: Close-up of the Danfoss MCI 15 Motor Controller's front panel, detailing the model number (MCI 15, 037N0039), electrical ratings, and adjustment potentiometers for ramp ຂຶ້ນ, ramp down, kick start, and initial torque.
ຂ້າງ view of the Danfoss MCI 15 Motor Controller showing the heat sink
ຮູບ 3.3: ຂ້າງ view of the Danfoss MCI 15 Motor Controller, highlighting the extensive heat sink design for thermal management.
ດ້ານຫລັງ view of the Danfoss MCI 15 Motor Controller with mounting brackets
ຮູບ 3.4: ດ້ານຫລັງ view of the Danfoss MCI 15 Motor Controller, showing the mounting brackets and the heat sink structure.

4. ຂໍ້ມູນຈໍາເພາະ

Key technical specifications for the Danfoss MCI 15 Motor Controller:

ພາລາມິເຕີມູນຄ່າ
ໝາຍເລກຕົວແບບMCI 15 (037N0039)
ອັນດັບປັດຈຸບັນ (Ie)Max 15 A AC 53a
ການຄວບຄຸມ Voltage (Uc)24-480 V AC/DC
ການດໍາເນີນງານ Voltage (Ue)380-480V 50/60Hz
insulation Voltage (Ui)660V
Impulse Withstand Voltage (Uimp)4 kV
ຂະໜາດສິນຄ້າ5 x 5 x 2 ນິ້ວ
ນ້ໍາຫນັກລາຍການ1.35 ປອນ
ວັດສະດຸCopper (heat sink)
Max Fuse50 A gL/gG
Overload Relay Trip Class10
HP Rating (400-480V)10 HP
Detailed wiring diagram and electrical ratings for Danfoss MCI 15 Motor Controller
ຮູບທີ 4.1: ລາຍລະອຽດ view of the wiring diagram and electrical specifications label on the Danfoss MCI 15 Motor Controller, including terminal designations (1/L1, 3/L2, 5/L3, 2/T1, 4/T2, 6/T3, A1, A2), wire size requirements, torque settings, and power ratings.
Technical data and certifications label for Danfoss MCI 15 Motor Controller
Figure 4.2: Close-up of the technical data and certifications label on the Danfoss MCI 15 Motor Controller, showing the ramp-up/ramp-down time graph, withstand current, HP rating, and regulatory listings (SP, cULus, CE).

5. ການຕິດຕັ້ງແລະການຕິດຕັ້ງ

5.1 ການຕິດຕັ້ງ

The Danfoss MCI 15 Motor Controller is designed for panel mounting. Ensure adequate ventilation around the heat sink to prevent overheating. Use appropriate fasteners through the mounting brackets shown in Figure 3.4.

5.2 ສາຍໄຟ

Refer to the wiring diagram on the device label (Figure 4.1) for correct connections. Ensure all wiring adheres to local electrical codes and safety standards.

  • Power Input (L1, L2, L3): Connect the three-phase power supply to terminals 1/L1, 3/L2, and 5/L3.
  • Motor Output (T1, T2, T3): Connect the motor leads to terminals 2/T1, 4/T2, and 6/T3.
  • Control Input (A1, A2): ເຊື່ອມຕໍ່ການຄວບຄຸມ voltage ກັບ terminals A1 ແລະ A2.
  • Use recommended wire sizes (e.g., 0.75-6mm² or 18-10AWG for power, 0.5-1.5mm² or 20-16AWG for control) and tighten terminals to the specified torque (e.g., 0.5Nm or 4.4lb-in for M3 screws).

5.3 ການຕັ້ງຄ່າເບື້ອງຕົ້ນ

Before initial operation, adjust the potentiometers on the front panel (Figure 3.2) to desired settings:

  • Ramp ເວລາຂຶ້ນ: Adjust the 'up' potentiometer to set the motor acceleration time (0-10 seconds).
  • Ramp Down Time: Adjust the 'down' potentiometer to set the motor deceleration time (0-10 seconds).
  • Kick Start: Adjust this potentiometer to provide an initial torque boost for starting loads.
  • Initial Torque: Adjust this potentiometer to set the initial torque level during startup.

6. ຄໍາແນະນໍາການດໍາເນີນງານ

Once installed and configured, the Danfoss MCI 15 Motor Controller operates by applying a controlled voltagເອີamp to the motor, providing a soft start and stop. The motor will accelerate to full speed over the set ramp-up time and decelerate over the set ramp- ເວ​ລາ​ລົງ​.

  • ນຳໃຊ້ການຄວບຄຸມ voltage to terminals A1 and A2 to initiate motor operation.
  • Remove control voltage to initiate motor stop (soft stop).
  • Monitor motor performance and adjust ramp times and torque settings as needed for optimal operation.

7. ບໍາລຸງຮັກສາ

Regular maintenance ensures the longevity and reliable operation of the motor controller.

  • ທໍາຄວາມສະອາດ: Periodically clean the exterior of the controller, especially the heat sink fins, to ensure proper heat dissipation. Use a dry, soft cloth. Do not use solvents or abrasive cleaners.
  • ການກວດກາ: Regularly inspect wiring connections for tightness and signs of wear or damage. Check for any discoloration or unusual odors, which may indicate overheating.
  • ສະພາບແວດລ້ອມ: ໃຫ້ແນ່ໃຈວ່າສະພາບແວດລ້ອມການເຮັດວຽກຍັງຄົງຢູ່ໃນຂອບເຂດອຸນຫະພູມແລະຄວາມຊຸ່ມຊື່ນທີ່ກໍານົດ.

8. ການແກ້ໄຂບັນຫາ

If the motor controller does not operate as expected, consider the following basic troubleshooting steps:

  • No Motor Start: Verify power supply to the controller and motor. Check control signal to A1/A2. Ensure all wiring is correct and secure.
  • Motor overheating: Check for proper ventilation around the heat sink. Ensure the motor is not overloaded. Verify motor parameters are correctly set.
  • Incorrect Ramp ເວລາ: Re-adjust the 'up' and 'down' potentiometers on the front panel.
  • Unexpected Stops: Check for power fluctuations or intermittent control signals. Inspect for any fault indicators if available on the device or system.

For complex issues, contact Danfoss technical support.

9. ການຮັບປະກັນແລະການສະຫນັບສະຫນູນ

ສຳລັບຂໍ້ມູນກ່ຽວກັບການຮັບປະກັນຜະລິດຕະພັນ, ການສະໜັບສະໜູນດ້ານວິຊາການ, ຫຼື ການບໍລິການ, ກະລຸນາອ້າງອີງເຖິງ Danfoss ຢ່າງເປັນທາງການ website or contact your local Danfoss representative. Ensure you have the model number (MCI 15) and serial number (if applicable, visible on the rear label, Figure 7.1) available when contacting support.

ຫລັງ view of Danfoss MCI 15 Motor Controller showing ID label
ຮູບ 9.1: ດ້ານຫລັງ view of the Danfoss MCI 15 Motor Controller, displaying a label with Type No., ID No., and Date of manufacture.

ເອກະສານທີ່ກ່ຽວຂ້ອງ - MCI 15

ກ່ອນview Danfoss VLT® Soft Starters: ຊ່ວງທີ່ສົມບູນແບບສໍາລັບການຄວບຄຸມມໍເຕີ AC
ສຳຫຼວດຊຸດ Danfoss VLT® Soft Starter, ລວມທັງ MCD 500, MCD 200, MCD 201, MCD 202, ແລະ MCD 100. ຄົ້ນພົບຄຸນສົມບັດ, ຂໍ້ມູນສະເພາະ, ແອັບພລິເຄຊັນ ແລະຂໍ້ມູນການສັ່ງຊື້ສຳລັບການຄວບຄຸມ ແລະການປ້ອງກັນມໍເຕີ AC ທີ່ໜ້າເຊື່ອຖື
ກ່ອນview Danfoss VLT® Soft Starter Selection Guide
A comprehensive guide to selecting and utilizing Danfoss VLT® Soft Starters, detailing their benefits, applications, product lines (Eltwin SMC, MCD 201, MCD 202, MCD 600), technical specifications, and ordering information. Learn how soft starters improve motor lifetime, reduce energy consumption, and protect equipment.
ກ່ອນview Danfoss VLT MCD 100 ຄູ່ມືການອອກແບບ Soft Starter
ຄູ່​ມື​ການ​ອອກ​ແບບ​ນີ້​ສະ​ຫນອງ​ຂໍ້​ມູນ​ທີ່​ສົມ​ບູນ​ແບບ​ກ່ຽວ​ກັບ​ການ Danfoss VLT MCD 100 ຊຸດ​ເລີ່ມ​ຕົ້ນ​ອ່ອນ​, ການ​ປົກ​ຫຸ້ມ​ຂອງ​ຄຸນ​ນະ​ສົມ​ບັດ​, ສະ​ເພາະ​ດ້ານ​ວິ​ຊາ​ການ​, ການ​ຄັດ​ເລືອກ​, ການ​ຕິດ​ຕັ້ງ​, ແລະ​ຄໍາ​ຮ້ອງ​ສະ​ຫມັກ examples ສໍາລັບການຄວບຄຸມມໍເຕີປະສິດທິພາບ.
ກ່ອນview Danfoss VLT® MCD 203 Series Compressor Starter Operating Instructions
This document provides operating instructions, specifications, wiring diagrams, and safety information for the Danfoss VLT® MCD 203 Series Compressor Starter.
ກ່ອນview Manual de Funcionamiento MCD 3000 Soft Starter
Este manual proporciona información detallada sobre el funcionamiento, instalación y programación del arrancador suave Danfoss MCD 3000. Incluye especificaciones técnicas, diagramas de cableado y guías de solución de problemas para asegurar una operación segura y eficiente.
ກ່ອນview Danfoss VLT MCD 202 Compact Starter: ຄູ່ມືການໃຊ້ງານ ແລະຂໍ້ມູນຈໍາເພາະ
ຄໍາ​ແນະ​ນໍາ​ການ​ປະ​ຕິ​ບັດ​ທີ່​ສົມ​ບູນ​ແບບ​, ສະ​ເພາະ​, ແຜນ​ວາດ​ສາຍ​, ແລະ​ຄູ່​ມື​ການ​ແກ້​ໄຂ​ບັນ​ຫາ​ສໍາ​ລັບ Danfoss VLT MCD 202 Compact Starter​. ຮຽນ​ຮູ້​ກ່ຽວ​ກັບ​ການ​ຕິດ​ຕັ້ງ​, ການ​ປັບ​, ແລະ​ລັກ​ສະ​ນະ​ຂອງ​ອຸ​ປະ​ກອນ​ການ​ຄວບ​ຄຸມ​ມໍ​ເຕີ​ນີ້​.