1. ການຕິດຕັ້ງແລະການຕິດຕັ້ງ
The AC Infinity CLOUDPLATE T9 is designed for installation in standard 19-inch equipment racks, occupying three rack units (3U) of space. Ensure adequate space and ventilation around the unit for optimal performance.
1.1 ເນື້ອໃນຊຸດ
ກ່ອນທີ່ຈະຕິດຕັ້ງ, ໃຫ້ກວດເບິ່ງວ່າອົງປະກອບທັງຫມົດແມ່ນຢູ່:
- CLOUDPLATE T9 Fan Unit
- Corded 6-ft Thermal Probe
- Rack Mount Screws
- ແກ່ນ ໝາກ ອຶ
- Corded 6-ft Power Supply

ຮູບທີ 1.1: Included accessories for the CLOUDPLATE T9, featuring the thermal probe, power supply, and mounting hardware.
1.2 ການຕິດຕັ້ງຫນ່ວຍງານ
- Identify the desired 3U rack space for installation. The unit is designed for exhaust airflow and should ideally be positioned near the top of the rack to effectively remove heated air.
- Align the mounting holes on the CLOUDPLATE T9 with the corresponding holes on your equipment rack.
- Secure the unit using the provided rack mount screws and cage nuts. Ensure the unit is firmly attached to prevent vibration.

ຮູບທີ 1.2: The CLOUDPLATE T9 unit securely mounted within an equipment rack.
1.3 Connecting the Thermal Probe and Power
- Connect the thermal probe to the designated port on the CLOUDPLATE T9 unit.
- Position the thermal probe within the rack where temperature monitoring is most critical, typically near heat-generating equipment. The probe cable is 6 feet long, allowing flexible placement.
- Connect the power supply to the unit and then plug it into a standard 100-240V AC outlet.

ຮູບທີ 1.3: ດ້ານໜ້າ view of the CLOUDPLATE T9, showcasing its digital display and fan grilles.
2. ຄໍາແນະນໍາການດໍາເນີນງານ
The CLOUDPLATE T9 features an intelligent LCD digital controller for precise temperature management and fan speed control.
2.1 ການຄວບຄຸມເກີນview
The front panel LCD displays current temperature, set temperature, fan speed, and various status indicators. Buttons allow for easy navigation and setting adjustments.

ຮູບທີ 2.1: ລະອຽດ view of the intelligent programming features on the CLOUDPLATE T9 controller.
2.2 ໂໝດການເຮັດວຽກ ແລະ ການຕັ້ງຄ່າ
The controller offers automated speed control and various programmable features:
- ໂModeດ SMART: Automatically adjusts fan speed in response to varying temperatures, optimizing cooling efficiency and noise levels.
- ໂໝດຄູ່ມື: Allows users to set a fixed fan speed from 1 to 6.
- ໂມງປຸກອຸນຫະພູມ: Configurable alerts for high temperatures.
- Fan Failure Triggers: Notifies users if a fan is not operating correctly.
- Power Savings Setting: ເພີ່ມປະສິດທິພາບການບໍລິໂພກພະລັງງານ.
- ຈໍສະແດງຜົນ Lock: ປ້ອງກັນການປ່ຽນແປງການຕັ້ງຄ່າໂດຍບັງເອີນ.
- ໜ່ວຍຄວາມຈຳສຳຮອງ: ຮັກສາການຕັ້ງຄ່າໃນລະຫວ່າງການເປີດປິດtages.
Refer to the on-screen menu for detailed instructions on adjusting specific settings.
2.3 Airflow and Cooling Principles
The CLOUDPLATE T9 is an exhaust fan system, designed to pull hot air out of the rack. For optimal cooling, it is recommended to have an intake fan system at the bottom of the rack to draw in cooler air, creating a consistent airflow path.

ຮູບທີ 2.2: Illustration of effective airflow management within an equipment rack using rack fans.
2.4 ການເຊື່ອມຕໍ່ຫຼາຍໜ່ວຍແບບ Daisy-Tchain
For enhanced cooling in larger setups, additional CLOUDPLATE units can be daisy-chained to share the same controller programming. This allows for synchronized operation and centralized control of multiple fan panels.
ວິດີໂອ 2.1: An official product video from AC Infinity demonstrating the features and benefits of the CLOUDPLATE Series rack mount cooling fan systems, including intelligent programming and daisy-chaining capabilities.
3. ບໍາລຸງຮັກສາ
Regular maintenance ensures the longevity and optimal performance of your CLOUDPLATE T9 unit.
3.1 ການທໍາຄວາມສະອາດ
Periodically inspect the fan grilles and blades for dust accumulation. Use a soft brush or compressed air to gently clean the surfaces. Ensure the unit is powered off before cleaning.
3.2 Fan Longevity
The CLOUDPLATE T9 features custom-engineered dual-ball bearing fans, rated for an L10 life expectancy of 67,000 hours. These bearings allow for reliable operation in both horizontal and vertical mounting positions.

ຮູບທີ 3.1: Illustration of the dual-ball bearing fan design, engineered for durability and quiet operation.
4. ການແກ້ໄຂບັນຫາ
This section addresses common issues you might encounter with your CLOUDPLATE T9.
ພັດລົມ 4.1 ບໍ່ເຮັດວຽກ
- ກວດສອບພະລັງງານ: ໃຫ້ແນ່ໃຈວ່າແຫຼ່ງຈ່າຍໄຟໄດ້ເຊື່ອມຕໍ່ກັບທັງເຄື່ອງ ແລະ ປລັກໄຟຟ້າທີ່ໃຊ້ງານໄດ້ຢ່າງປອດໄພ.
- ການຕັ້ງຄ່າຕົວຄວບຄຸມ: Verify that the fan speed is not set to zero or that the unit is not in a mode that keeps fans off (e.g., if the temperature is below the set threshold in SMART mode).
- Fan Failure Warning: If a fan failure warning is displayed, inspect the individual fans for obstructions or damage.
4.2 ສຽງດັງເກີນໄປ
- ຄວາມໄວພັດລົມ: Higher fan speeds (levels 4-6) will naturally produce more noise. Consider using SMART mode to allow the unit to adjust speed based on temperature, often resulting in quieter operation.
- ອຸປະສັກ: Ensure no cables or other objects are interfering with the fan blades.
- ການຕິດຕັ້ງ: Verify the unit is securely mounted and not vibrating against the rack frame.
4.3 Ineffective Cooling
- Airflow Path: Confirm that there is a clear path for cool air intake (typically at the bottom of the rack) and hot air exhaust (at the CLOUDPLATE T9). Blocked vents or equipment can hinder airflow.
- Thermal Probe Placement: Ensure the thermal probe is positioned accurately to measure the hottest area within the rack.
- ຄວາມໄວພັດລົມ: Increase the fan speed or adjust SMART mode settings to a lower target temperature if equipment is still overheating.
5. ຂໍ້ມູນຈໍາເພາະ
5.1 ການກໍານົດຜະລິດຕະພັນ
| ຜູ້ຜະລິດ | AC Infinity Inc. |
| ຊື່ຜະລິດຕະພັນ | CLOUDPLATE T9 |
| ຮູບແບບຜະລິດຕະພັນ | AI-CPT9 |
| ລະຫັດ UPC | 819137020023 |
5.2 Product and Mounting Dimensions
| ຂະ ໜາດ ທັງ ໝົດ | 19.0 x 5.25 x 2.0 ນິ້ວ (48.3 x 13.3 x 5.2 ຊມ) |
| Rack Mount Size | Three Rack Units (3U) |
| Screw Hole Size | Ø .24 x 0.35 in. (Ø 6.1 x 9.0 mm) |
| Obround Hole to Hole Distance | ຂະ ໜາດ 18.2 x 2.25 ນິ້ວ. (46.4 x 5.7 ຊມ) |
| ຂະຫນາດຈໍສະແດງຜົນ | ຂະ ໜາດ 2.25 x 1.25 ນິ້ວ. (4.7 x 3.2 ຊມ) |
| ຄວາມຍາວຂອງການກວດສອບ | 72 in. (6 feet) |
| ຄວາມຍາວສາຍ | 72 in. (6 feet) |

ຮູບທີ 5.1: Dimensional specifications of the CLOUDPLATE T9 unit.
5.3 Product Performance and Technical Specs
| ການອອກແບບ | ໄອເສຍ |
| ກະແສລົມທັງໝົດ | 60 ຫາ 300 CFM |
| ສຽງລົບກວນທັງໝົດ | 12 ຫາ 38 dBA |
| ຄວາມກົດດັນຄົງທີ່ | 2.56 ມມ-H2O |
| ການດໍາເນີນງານ Voltage | 12V DC |
| ພະລັງງານ | 12 ວ |
| ປະຈຸບັນ | 1 ກ |
| Wall Adapter Input | 100 ຫາ 240V AC |
| ຄວາມຊຸ່ມຊື່ນປະຕິບັດການ | 35 ຫາ 85% RH |
| ອຸນຫະພູມປະຕິບັດການ | 0 ຫາ 158°F |
| ພັດລົມ Bearings | ບານຄູ່ |
| ຕໍາແຫນ່ງການຕິດຕັ້ງ | ນອນຫຼືແນວຕັ້ງ |
| L10 Life Expectancy | 67,000 ຊົ່ວໂມງ |
| ວັດສະດຸ | ອາລູມີນຽມ |
6. ການຮັບປະກັນແລະການສະຫນັບສະຫນູນ
The AC Infinity CLOUDPLATE T9 is manufactured with high-quality components, including dual-ball bearing fans designed for a long operational life of 67,000 hours.
For specific warranty information, technical support, or service inquiries, please refer to the official AC Infinity webເວັບໄຊ ຫຼືຕິດຕໍ່ບໍລິການລູກຄ້າຂອງເຂົາເຈົ້າໂດຍກົງ. ຮັກສາໃບຮັບເງິນການຊື້ຂອງທ່ານສໍາລັບການຮ້ອງຂໍການຮັບປະກັນ.