Notifier FMM-1

Notifier FMM-1 Intelligent Addressable Monitor Module User Manual

Model: FMM-1

1. ການແນະນໍາ ແລະຫຼາຍກວ່າview

The Notifier FMM-1 is an intelligent addressable monitor module designed for use with Notifier's ONYX series and other compatible fire alarm control panels. This module allows conventional alarm initiating devices, such as manual pull stations, normally open contact devices, or waterflow switches, to be connected to an intelligent fire alarm system. It monitors the status of these devices and reports their condition (normal, alarm, or trouble) back to the control panel.

The FMM-1 module is a crucial component for integrating existing conventional devices into modern addressable fire detection systems, providing precise location identification for alarms and troubles.

ດ້ານໜ້າ view of the Notifier FMM-1 Intelligent Addressable Monitor Module, showing the Notifier by Honeywell logo and two small indicator lights.

ຮູບ 1: ດ້ານຫນ້າ view of the Notifier FMM-1 module. This image displays the module's front face, featuring the "Notifier by Honeywell" branding and two small circular indicators, likely for status or activity.

2. ການຕິດຕັ້ງແລະການຕິດຕັ້ງ

Installation of the FMM-1 module should only be performed by qualified personnel in accordance with all local and national electrical codes, and the manufacturer's instructions. Ensure that all power to the fire alarm control panel and associated circuits is disconnected before beginning installation.

2.1 ການຕິດຕັ້ງ

The FMM-1 module is designed for mounting in a standard 4-inch square, 2-1/8 inch deep electrical box. It can also be mounted in a surface-mount box (SMB500) or a standard 1-gang box. The module includes mounting tabs for secure installation.

ດ້ານໜ້າ ແລະ ດ້ານຫຼັງ view of the Notifier FMM-1 module, showing the white plastic cover and the grey metal base with wiring terminals.

Figure 2: Front and back components of the Notifier FMM-1 module. This image illustrates both the front cover and the rear mounting plate, which houses the terminal connections for wiring.

2.2 ສາຍໄຟ

The FMM-1 module connects to the Signaling Line Circuit (SLC) of the fire alarm control panel and to the conventional initiating device circuit (IDC). Refer to the specific wiring diagrams provided with the module and the fire alarm control panel for correct connections. Ensure proper polarity for all connections.

Close-up of the back of the Notifier FMM-1 module, showing wiring terminals, model number, and regulatory markings like UL Listed and FM Approved.

ຮູບ 3: ດ້ານຫລັງ view of the Notifier FMM-1 module with wiring details. This image provides a clear view of the terminal block for connecting to the fire alarm system's Signaling Line Circuit (SLC) and the initiating device circuit (IDC), along with product labels and certifications.

After wiring, verify all connections are secure and correct before applying power to the system.

3. ຫຼັກການດຳເນີນງານ

Once properly installed and addressed, the FMM-1 module operates by continuously monitoring the connected conventional initiating device circuit. It communicates the status of this circuit to the intelligent fire alarm control panel via the SLC.

The module's LED indicators (if present) may provide local visual indication of its status, such as flashing during normal operation or solid during an alarm/trouble condition. Refer to the specific product documentation for LED behavior.

4. ບໍາລຸງຮັກສາ

The Notifier FMM-1 module is designed for reliable, long-term operation with minimal maintenance. However, regular system-wide inspections and testing are crucial for ensuring the continued proper functioning of the fire alarm system.

Any maintenance or repair work beyond simple visual inspection and cleaning should be performed by a certified fire alarm technician.

5. ການແກ້ໄຂບັນຫາ

If the FMM-1 module or its connected devices are not functioning as expected, consider the following troubleshooting steps. Always ensure power is disconnected before inspecting wiring.

ອາການສາເຫດທີ່ເປັນໄປໄດ້ການແກ້ໄຂ
Module reports trouble condition.Open circuit, short circuit, or ground fault on IDC; incorrect EOLR; module addressing error.Verify IDC wiring for breaks or shorts. Check EOLR value and placement. Confirm module address is unique and correctly set.
Module not communicating with control panel.Incorrect SLC wiring; module address conflict; faulty module.Check SLC wiring for proper polarity and continuity. Ensure no duplicate addresses on the SLC. If issues persist, module may need replacement.
Connected device does not report alarm.Faulty initiating device; incorrect IDC wiring; module not configured correctly.Test the initiating device directly. Verify IDC wiring to the device. Confirm module programming in the control panel.

For complex issues or if troubleshooting steps do not resolve the problem, contact a certified fire alarm technician or Notifier technical support.

6. ຂໍ້ມູນຈໍາເພາະ

The following are key specifications for the Notifier FMM-1 Intelligent Addressable Monitor Module:

Notifier FMM-1 module in its original packaging, alongside a small instruction manual and a few small components.

Figure 4: Notifier FMM-1 module as packaged. This image shows the module, its clear plastic packaging, and the included installation and maintenance instructions, along with minor accessories.

7. ການຮັບປະກັນແລະການສະຫນັບສະຫນູນ

For specific warranty information regarding the Notifier FMM-1 Intelligent Addressable Monitor Module, please refer to the warranty documentation provided with your purchase or contact your authorized Notifier distributor or reseller. Warranty terms typically cover defects in materials and workmanship for a specified period from the date of purchase.

For technical support, installation assistance, or service inquiries, please contact Notifier's official customer support channels or your certified fire alarm system installer. Always provide your product model number (FMM-1) and any relevant system details when seeking support.

Notifier Official Webເວັບໄຊ: www.notifier.com

ເອກະສານທີ່ກ່ຽວຂ້ອງ - FMM-1

ກ່ອນview ລະບົບເຕືອນໄຟໄໝ້ອັດສະລິຍະ NOTIFIER NFS-3030 | ເອກະສານຂໍ້ມູນດ້ານວິຊາການ
ສຳຫຼວດ NOTIFIER NFS-3030, ແຜງຄວບຄຸມສັນຍານເຕືອນໄຟໄໝ້ທີ່ສາມາດລະບຸທີ່ຢູ່ໄດ້ຢ່າງສະຫຼາດຈາກຊຸດ ONYX. ອອກແບບມາສຳລັບສະຖານທີ່ຂະໜາດກາງຫາຂະໜາດໃຫຍ່, ມັນສະເໜີການກວດຈັບຂັ້ນສູງ, ຄວາມສາມາດແບບໂມດູນ ແລະ ການຮອງຮັບອຸປະກອນຢ່າງກວ້າງຂວາງສຳລັບການນຳໃຊ້ດ້ານຄວາມປອດໄພຈາກໄຟໄໝ້ທີ່ສຳຄັນ.
ກ່ອນview Notifier NFS-320 Intelligent Addressable ຂໍ້ມູນລະບົບເຕືອນໄພໄຟໄໝ້
ເອກະສານຂໍ້ມູນທີ່ສົມບູນແບບສໍາລັບ Notifier NFS-320 Intelligent Addressable Fire Alarm System, ລາຍລະອຽດຄຸນສົມບັດຂອງມັນ, ຄວາມສາມາດໃນການຮັບຮູ້ອັດສະລິຍະ, FlashScan protocol, ຂໍ້ມູນຈໍາເພາະຂອງລະບົບ, ອຸປະກອນທີ່ເຂົ້າກັນໄດ້, ແລະການອະນຸມັດຂອງອົງການ.
ກ່ອນview Notifier NFS-640 Intelligent Addressable ຂໍ້ມູນລະບົບເຕືອນໄພໄຟໄໝ້
ລະອຽດview of the Notifier NFS-640 Intelligent Addressable Fire Alarm Control Panel, covering its features, advanced FlashScan® protocol, intelligent sensing capabilities, programming options, system modules, and comprehensive technical specifications.
ກ່ອນview Notifier AM-8000 Intelligent Addressable Fire Detection Manual
ຄູ່ມືການຕິດຕັ້ງນີ້ໃຫ້ຄໍາແນະນໍາທີ່ສົມບູນແບບສໍາລັບລະບົບ Notifier AM-8000 Intelligent Addressable Fire Detection. ມັນກວມເອົາລະບົບຫຼາຍກວ່າview, ສະເພາະດ້ານວິຊາການ, ລັກສະນະໄຟຟ້າ, ຂັ້ນຕອນການຕິດຕັ້ງ, ແຜນວາດສາຍໄຟ, ການຄິດໄລ່ການສະຫນອງພະລັງງານ, ການທົດສອບ, ແລະການບໍາລຸງຮັກສາ.
ກ່ອນview NOTIFIER AFP-200 Analog Fire Panel - Technical Specifications and Features
ລະອຽດview of the NOTIFIER AFP-200 Analog Fire Panel, covering its features, system capacity, specifications, compatible devices, and programming methods. Includes agency listings and product information.
ກ່ອນview ແຜງຄວບຄຸມສັນຍານເຕືອນໄຟທີ່ອັດສະລິຍະ AFC-600 ອັດສະລິຍະດ້ວຍແຜ່ນຂໍ້ມູນ FlashScan®
ເອກະສານຂໍ້ມູນທີ່ສົມບູນແບບສໍາລັບກະດານຄວບຄຸມສັນຍານເຕືອນໄຟທີ່ອັດສະລິຍະ AFC-600 ອັດສະລິຍະ, ລາຍລະອຽດກ່ຽວກັບຄຸນສົມບັດ, ຂໍ້ມູນສະເພາະ, ຄວາມອາດສາມາດຂອງລະບົບ, ຕົວເລືອກການຂຽນໂປຣແກຣມ, ອຸປະກອນທີ່ເຂົ້າກັນໄດ້, ແລະການອະນຸມັດຂອງອົງການ. ຮວມເອົາຂໍ້ມູນກ່ຽວກັບໂປຣໂຕຄໍ FlashScan® ແລະເທັກໂນໂລຍີການຮັບຮູ້ຂອງ AWACS™™.